DZ47-100 DZ47-125 NC125H 1P 2P 3P 4P 80A 100A 125A MCB 1 pole 2 pole 3 pole 100 Amp 125 Amp Mini Circuit Breaker
1. Application
DZ47-125 mini circuit breaker is such features as delicate appearance, light weight, excellent and reliableperformance, high breaking capacity, rapid tripping and mounted by rail. Its enclosure and com-ponents adopts high fire-retarding and shock-resistance plastic of long durability. It mainly servesfor protecting the circuits of AC 50Hz, 230V of single pole, 400V of two poles or three or fourpoles from overload or short-circuit, and also for unfrequent making and breaking electricalapparatus and lighting circuit.It conforms with the standards of IEC60947-2.
2. Main Technical Parameter
| Type | DZ47-125 | |
| Pole | 1P | 2P, 3P, 4P |
| Rated current | 63, 80, 100,125A | |
| Rated voltage | 230V | 400V |
| Ambient temperature | -5oC~+40oC | |
| Type of instantaneous release | C, D | |
| Rated short circuit breaking capacity Icn | 6kA | |
3. The over-current protection property
| Ambient Temperature | Initial Status | Test Current | Expected Result | Expected Result | Note |
| 40±2oC | Cold position | 1.05In(In≤63A) | t≤1h | Non-release | – |
| Cold position | 1.05In (In[63A) | t≤2h | Non-release | – | |
|
Carried out immedi-ately after previous test |
1.30In(In≤63A) | t < 1h | Release | Current smoothlyrises to specified value within 5s | |
| 1.30In (In>63A) | t < 2h | Release | |||
| -5~+40oC | Cold position | 8.00In | t≤0.2s | Non-release | – |
| Cold position | 12.00In | t< 0.2s | Non-release | – |
4. Applicable conducting wire
| Rated current(A) | Nominal cross section of wire mm2 |
| 63A | 16 |
| 80A | 25 |
| 100A | 35 |
5. Dimension