Product Overview
The ZT-830 Series Intelligent Capacitor Controller is a new generation reactive power compensation controller designed with a special power parameter acquisition chip and MCU processor. It is specially designed to control Intelligent Capacitors via RS485 communication, providing automated power factor optimization and power quality improvement for low-voltage distribution systems.
Main Features
- LED Digital Display: Clear digital tube display with simple key operation for easy configuration
- RS485 Communication: Seamless integration with CHINT BAGB/BAFB Intelligent Capacitors via RS485 data cable
- Auto-Detection: Automatically detects the number and capacity of connected Intelligent Capacitors
- Smart Control: Controls capacitor switching based on reactive power parameters of the power grid
- Comprehensive Protection: Over-voltage, under-voltage, voltage warning, under-current, over-temperature, and over-harmonic protection
- Quick Response: Rapidly cuts off capacitors and locks output when grid parameters exceed limits
- Accurate Compensation: Multi-contact sampling with voltage return difference for precise control judgment
- Plug-and-Play: Network control enables fast system commissioning
Technical Specifications
| Parameter | Specification |
|---|---|
| Working Voltage | AC380V ±20% |
| Rated Frequency | 50Hz ±5% |
| Power Consumption | < 5W |
| Voltage Measurement Accuracy | ≤±0.5% (80%~120% rated voltage) |
| Current Measurement Accuracy | ≤±1% (50%~100% rated current) |
| Power Factor Accuracy | ≤±1.5% |
| Reactive Power Accuracy | ≤±2% |
| Output Mode | RS485 Communication Control |
| Communication Protocol | RS485 Modbus |
| Max Capacitors (ZT-830GB) | ≤30 sets simultaneous compensation |
| Max Capacitors (ZT-830FB) | ≤10 phase-splitting + ≤20 simultaneous |
| Installation Opening Size | 113 × 113mm |
Technical and Application Notes
The ZT-830 controller performs comprehensive calculations on voltage, current, power factor, and reactive power. The voltage return difference participates in the control judgment to make compensation more accurate and prevent switching oscillation. Multi-contact sampling within the action delay time judges reactive power trends to avoid errors caused by single-contact sampling.
Model Selection: ZT-830GB is designed for three-phase simultaneous compensation, while ZT-830FB supports both simultaneous and phase-splitting hybrid compensation modes. Choose the appropriate model based on your reactive power compensation requirements.
Typical Applications
- Reactive power compensation systems
- Power factor optimization
- Low-voltage distribution systems
- Industrial power quality improvement
- Commercial building electrical systems
- Manufacturing facility power management
Ordering Support
When ordering ZT-830 series controllers, please specify:
- Model type: ZT-830GB (simultaneous) or ZT-830FB (hybrid)
- Number of capacitor sets to be controlled
- System voltage and configuration
- Compatible capacitor models (BAGB/BAFB series)
The ZT-830 series is designed to work seamlessly with CHINT’s BAGB and BAFB intelligent LV shunt capacitors for complete reactive power compensation solutions.
Product Catalog
For detailed technical drawings, dimensions, and additional specifications, please refer to the product catalog below.