NewTrend LC1K0610M7 3P AC3 6A 1NO aux 220V 230V AC coil Contactor
| Main | |
| product or component type |
LC1K0610M7 Contactor
|
| product brand |
NewTrend
|
| device application |
Control
|
| contactor application |
Motor control
|
| Complementary | |
| utilisation category |
AC-3
|
| AC-4 | |
| poles description |
3P
|
| power pole contact composition |
3 NO
|
| [Ue] rated operational voltage |
Power circuit: 690 V AC 50/60 Hz
|
| Signalling circuit: <= 690 V AC 50/60 Hz | |
| [Ie] rated operational current |
6 A at <= 440 V AC AC-3 for power circuit
|
| control circuit type |
AC at 50/60 Hz
|
| [Uc] control circuit voltage |
220…230 V AC 50/60 Hz
|
| motor power kW |
1.5 kW at 220…230 V AC 50/60 Hz AC-3
|
| 2.2 kW at 380…415 V AC 50/60 Hz AC-3 | |
| 3 kW at 440 V AC 50/60 Hz AC-3 | |
| 3 kW at 480 V AC 50/60 Hz AC-3 | |
| 3 kW at 500…600 V AC 50/60 Hz AC-3 | |
| 3 kW at 660…690 V AC 50/60 Hz AC-3 | |
| 1.5 kW at 400 V AC 50/60 Hz AC-4 | |
| auxiliary contact composition |
1 NO
|
| [Uimp] rated impulse withstand voltage |
8 kV
|
| overvoltage category |
III
|
| [Ith] conventional free air thermal current |
20 A (at 50 °C) for power circuit
|
| 10 A (at 50 °C) for signalling circuit | |
| Irms rated making capacity |
110 A AC for power circuit conforming to NF C 63-110
|
| 110 A AC for power circuit conforming to IEC 60947 | |
| 110 A AC for signalling circuit conforming to IEC 60947 | |
| rated breaking capacity |
110 A at 415 V conforming to IEC 60947
|
| 110 A at 440 V conforming to IEC 60947 | |
| 80 A at 500 V conforming to IEC 60947 | |
| 110 A at 220…230 V conforming to IEC 60947 | |
| 110 A at 380…400 V conforming to IEC 60947 | |
| 70 A at 660…690 V conforming to IEC 60947 | |
| [Icw] rated short-time withstand current |
90 A 50 °C – 1 s for power circuit
|
| 85 A 50 °C – 5 s for power circuit | |
| 80 A 50 °C – 10 s for power circuit | |
| 60 A 50 °C – 30 s for power circuit | |
| 45 A 50 °C – 1 min for power circuit | |
| 40 A 50 °C – 3 min for power circuit | |
| 20 A 50 °C – >= 15 min for power circuit | |
| 80 A – 1 s for signalling circuit | |
| 90 A – 500 ms for signalling circuit | |
| 110 A – 100 ms for signalling circuit | |
| associated fuse rating |
25 A gG at <= 440 V for power circuit
|
| 25 A aM for power circuit | |
| 10 A gG for signalling circuit conforming to IEC 60947 | |
| 10 A gG for signalling circuit conforming to VDE 0660 | |
| average impedance |
3 mOhm – Ith 20 A 50 Hz for power circuit
|
| [Ui] rated insulation voltage |
Power circuit: 600 V conforming to UL 508
|
| Power circuit: 690 V conforming to IEC 60947-4-1 | |
| Signalling circuit: 690 V conforming to IEC 60947-4-1 | |
| Signalling circuit: 690 V conforming to IEC 60947-5-1 | |
| Signalling circuit: 600 V conforming to UL 508 | |
| Power circuit: 600 V conforming to CSA C22.2 No 14 | |
| Signalling circuit: 600 V conforming to CSA C22.2 No 14 | |
| insulation resistance |
> 10 MOhm for signalling circuit
|
| inrush power in VA |
30 VA (at 20 °C)
|
| hold-in power consumption in VA |
4.5 VA (at 20 °C)
|
| heat dissipation |
1.3 W
|
| control circuit voltage limits |
Operational: 0.8…1.15 Uc (at <50 °C)
|
| Drop-out: 0.2…0.75 Uc (at <50 °C) | |
| connections – terminals |
Screw clamp terminals 1 cable(s) 1.5…4 mm²solid
|
| Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable end | |
| Screw clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable end | |
| Screw clamp terminals 2 cable(s) 1.5…4 mm²solid | |
| Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end | |
| Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end | |
| maximum operating rate |
3600 cyc/h
|
| auxiliary contacts type |
type instantaneous 1 NO
|
| signalling circuit frequency |
<= 400 Hz
|
| minimum switching current |
5 mA for signalling circuit
|
| minimum switching voltage |
17 V for signalling circuit
|
| mounting support |
Rail
|
| Plate | |
| tightening torque |
1.3 N.m – on screw clamp terminals – with screwdriver Philips No 2
|
| 1.3 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm | |
| operating time |
10…20 ms coil de-energisation and NO opening
|
| 10…20 ms coil energisation and NO closing | |
| safety reliability level |
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
|
| B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 | |
| non overlap distance |
0.5 mm
|
| mechanical durability |
10 Mcycles
|
| electrical durability |
1.3 Mcycles 6 A AC-3 at Ue <= 440 V
|
| mechanical robustness |
Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
|
| Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 | |
| Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 | |
| Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 | |
| Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 | |
| Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 | |
| Vibrations contactor closed: 4 Gn, 5…300 Hz conforming to IEC 60068-2-6 | |
| Vibrations contactor opened: 2 Gn, 5…300 Hz conforming to IEC 60068-2-6 | |
| height |
58 mm
|
| width |
45 mm
|
| depth |
57 mm
|
| net weight |
0.18 kg
|
| Environment | |
| standards |
BS 5424
|
| IEC 60947 | |
| NF C 63-110 | |
| VDE 0660 | |
| product certifications |
CE
|
| IP degree of protection |
IP2x conforming to VDE 0106
|
| protective treatment |
TC conforming to IEC 60068
|
| TC conforming to DIN 50016 | |
| ambient air temperature for storage |
-50…80 °C
|
| operating altitude |
2000 m without derating
|
| flame retardance |
V1 conforming to UL 94
|
| Requirement 2 conforming to NF F 16-101 | |
| Requirement 2 conforming to NF F 16-102 | |