LC1D258E7 LC1D258E7C Contactor
| Main | |
| range |
TeSys
|
| product name |
TeSys D
|
| product or component type |
Contactor
|
| device short name |
LC1D
|
| contactor application |
Resistive load
|
| utilisation category |
AC-1
|
| poles description |
4P
|
| power pole contact composition |
2 NO + 2 NC
|
| [Ue] rated operational voltage |
Power circuit: <= 690 V AC 25…400 Hz
|
| Power circuit: <= 300 V DC | |
| [Ie] rated operational current |
40 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
|
| control circuit type |
AC at 50/60 Hz
|
| [Uc] control circuit voltage |
48 V AC 50/60 Hz
|
| auxiliary contact composition |
1 NO + 1 NC
|
| [Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947
|
| overvoltage category |
III
|
| [Ith] conventional free air thermal current |
10 A (at 60 °C) for signalling circuit
|
| 40 A (at 60 °C) for power circuit | |
| Irms rated making capacity |
140 A AC for signalling circuit conforming to IEC 60947-5-1
|
| 250 A DC for signalling circuit conforming to IEC 60947-5-1 | |
| 450 A at 440 V for power circuit conforming to IEC 60947 | |
| rated breaking capacity |
450 A at 440 V for power circuit conforming to IEC 60947
|
| [Icw] rated short-time withstand current |
240 A 40 °C – 10 s for power circuit
|
| 380 A 40 °C – 1 s for power circuit | |
| 50 A 40 °C – 10 min for power circuit | |
| 120 A 40 °C – 1 min for power circuit | |
| 100 A – 1 s for signalling circuit | |
| 120 A – 500 ms for signalling circuit | |
| 140 A – 100 ms for signalling circuit | |
| associated fuse rating |
10 A gG for signalling circuit conforming to IEC 60947-5-1
|
| 63 A gG at <= 690 V coordination type 1 for power circuit | |
| 40 A gG at <= 690 V coordination type 2 for power circuit | |
| average impedance |
2 mOhm – Ith 40 A 50 Hz for power circuit
|
| [Ui] rated insulation voltage |
Power circuit: 690 V conforming to IEC 60947-4-1
|
| Power circuit: 600 V CSA certified | |
| Power circuit: 600 V UL certified | |
| Signalling circuit: 690 V conforming to IEC 60947-1 | |
| Signalling circuit: 600 V CSA certified | |
| Signalling circuit: 600 V UL certified | |
| electrical durability |
1.4 Mcycles 40 A AC-1 at Ue <= 440 V
|
| power dissipation per pole |
3.2 W AC-1
|
| Front cover |
With
|
| mounting support |
Rail
|
| Plate | |
| standards |
CSA C22.2 No 14
|
| EN 60947-4-1 | |
| EN 60947-5-1 | |
| IEC 60947-4-1 | |
| IEC 60947-5-1 | |
| UL 508 | |
| tightening torque |
Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm
|
| Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver Philips No 2 | |
| Power circuit: 1.8 N.m – on connector – with screwdriver flat Ø 6 mm | |
| Power circuit: 1.8 N.m – on connector – with screwdriver Philips No 2 | |
| operating time |
12…22 ms closing
|
| 4…19 ms opening | |
| safety reliability level |
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
|
| B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 | |
| mechanical durability |
15 Mcycles
|
| maximum operating rate |
3600 cyc/h 60 °C
|
| Complementary | |
| coil technology |
Without built-in suppressor module
|
| control circuit voltage limits |
0.3…0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz
|
| 0.8…1.1 Uc (-40…60 °C):operational AC 50 Hz | |
| 0.85…1.1 Uc (-40…60 °C):operational AC 60 Hz | |
| 1…1.1 Uc (60…70 °C):operational AC 50/60 Hz | |
| inrush power in VA |
70 VA 60 Hz cos phi 0.75 (at 20 °C)
|
| 70 VA 50 Hz cos phi 0.75 (at 20 °C) | |
| hold-in power consumption in VA |
7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
|
| 7 VA 50 Hz cos phi 0.3 (at 20 °C) | |
| heat dissipation |
2…3 W at 50/60 Hz
|
| auxiliary contacts type |
type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
|
| type mirror contact 1 NC conforming to IEC 60947-4-1 | |
| signalling circuit frequency |
25…400 Hz
|
| minimum switching current |
5 mA for signalling circuit
|
| minimum switching voltage |
17 V for signalling circuit
|
| non-overlap time |
1.5 ms on de-energisation between NC and NO contact
|
| 1.5 ms on energisation between NC and NO contact | |
| insulation resistance |
> 10 MOhm for signalling circuit
|
| contact compatibility |
M6
|
| compatibility code |
LC1D
|
| Environment | |
| IP degree of protection |
IP20 front face conforming to IEC 60529
|
| protective treatment |
TH conforming to IEC 60068-2-30
|
| pollution degree |
3
|
| ambient air temperature for operation |
-40…60 °C
|
| 60…70 °C with derating | |
| ambient air temperature for storage |
-60…80 °C
|
| operating altitude |
0…3000 m
|
| fire resistance |
850 °C conforming to IEC 60695-2-1
|
| height |
105 mm
|
| width |
45 mm
|
| depth |
99 mm
|
| net weight |
0.425 kg
|
| Packing Units | |